NET VISION 2010 THREE-PHASE NETWORK ANALYZER WITH ONE CURRENT CLAMP TO 100A (or to1000A)

THREE-PHASE NETWORK ANALYZER WITH ONE CURRENT CLAMP TO 100A (or to1000A)

Application and brief description

NET VISION 2010 is a portable device designed for a quick and precise measurement of the electric values of a three-phase network. It is used by power engineers for check of AC motors, relay current protections, electricity meters, etc.

The true RMS values of the three-phases of voltage and one current are measured simultaneously. Active power, reactive power, power factor, sequence of rotation, frequency, phase angle between two voltages, phase angle between voltage and current, peak values, crest factor are computed and indicated.

There are also other modes in which the device can draw the vector diagram, two waveforms in real time or indicate harmonic analysis. The current is measured with a current clamp to 100 A (or to 1000A by a special order).

The values and the waveforms are indicated on a graphic LCD display.

The device can work without batteries - it is supplied from the measuring circuit of the voltages.

Features

Indication of the measured values

Mode - "Indication of the measured values" (Fig.1)

The sequence of rotation and the frequency of the net are displayed permanently in this mode. Five more parameters are also displayed, which could be changed by the operator.

Two beam oscilloscope

Mode - "Two beam oscilloscope" (Fig.2)

Two waveforms in real time are drawn on the graphic display in this mode. The operator can choose the waveforms from the three voltages and one current.

Vector diagram

Mode - "Vector diagram" (Fig.3)

The three voltages and the current are drawn as a vector diagram in this mode.

Harmonic analysis

Mode - "Harmonic analysis" (Fig.4)

Indication of the harmonics to 15th of one signal in real time.

Option - RS 232

The values in each mode are changed in every two seconds

Technical data

Range of voltage (with auto sub ranges)
50V ÷ 275 V RMS
5V ÷ 275 V RMS (power supply - batteries)
Range of current (with auto sub ranges)
Current clamp to 1000 A 0.2 ÷ 1000 A RMS
Current clamp to 100 A 0.02 ÷100 A RMS
Instrumental error
Voltage measurement ± 0.1 [%]
Current measurement ± 0.4 [%]
Power measurement ± 0.5/ cos f [%]
Measurement of phase angle
between two voltages
± 0.1°
Measurement of phase angle
between one voltage and current
± 1°
Power supply
from the measuring circuit (50V to 275V)
from 4 batteries x 1.5 V
Graphic LCD display128 x 64 pixels
Dimensions 190 x 90 x 60 mm
Weight 0.5 Kg
Jaw capacity of the current clamp 100 A-12 mm diameter

Safety and Electromagnetic compatibility

The model complies with IEC 1010 - 1, 600V CAT IV for safety; EN 50082 - 1, EN 61000 - 4 - 2, IEC CISPR 22 for electromagnetic compatibility.

Equipment completion